Products Name: LSK System Electric Control Cabinet
Conditions of use: Suitable for conveying the temperature under 60 celsius water and similar to that of liquid water, pump system working pressure of up to 11 bar.
The scope of performance parameter: This series a total of 6 species, 50kinds of specifications and its
performance parameters range:
1 flow Q= 18~108 m3/h
2. Lift H= 30 ~ 160 m
3. Speed n=1450/2900 r/mi8
4. Power P=1.1~ 274kW
fault phenomenon | failure cause | elimination methods |
The manual is normal Automatic transmission failure | 1.No power supply or one or two phase power supply is needed | Check all phases of power supply and restore power supply |
Water level is too low | Put water in the sink | |
The motor burned | Repair or replace the motor | |
1.Line is loose | Check wiring and tighten connectors | |
2.Frequency converter malfunction | Check the fault content, check the cause according to the frequency converter manual, and restart after reset.Or disconnect the inverter power supply for a few seconds, the inverter fault reset before starting. | |
3The frequency converter is damaged | Repair or replace | |
4.Pressure switch damage | Repair or replace | |
5The pressure transmitter is damaged | Repair or replace | |
6.Switch failure | Repair or replace | |
Pump non - suction pressure gauge pointer to beat violently | Insufficient water supply for perfusion, air leakage at the connection between pipeline and instrument | Check pipeline and bottom valve, refill water diversion. Tighten air leakage |
The pump consumes too much power | Too much flow, impeller wear | Check whether the pump shaft is bent, replace the impeller, close the outlet valve to reduce the flow |